Standards and compliance
What is checked
Selecting an activity for a room loads its criteria and the design is assessed against them. Each check reports the measured value, the requirement, the margin and a verdict.
| Check | Basis | Notes | | --- | --- | --- | | Maintained illuminance | Task area average | Initial illuminance times the maintenance factor | | Over-illumination | 30 per cent above the requirement | Not a failure, flagged as wasted energy | | Overall uniformity Uo | Emin / Eavg on the task area | Boundary band excluded | | Diversity Ud | Emin / Emax on the task area | Good practice, not a formal limit | | UGR | Worst observer position and direction | CIE 117 | | Cylindrical illuminance | Mean Ez at 1.2 m | EN 12464-1:2021 modelling requirement | | Surrounding area | Declared surround zone, or the whole room as a proxy | Graded scale when the table states no value | | Wall illuminance | Mean maintained on the walls, 50 lx | EN 12464-1:2021 interior workplaces | | Ceiling illuminance | Mean maintained on the ceiling, 30 lx | Needs an upward or wall-reflected component | | Colour rendering | Lowest Ra in the fixture schedule | Taken from the product records | | Grid spacing | Against the EN 12464-1 maximum | A coarse grid can miss the true minimum | | Lighting power density | Installed load divided by design area | Against the allowance for the space type | | Average daylight factor | 2 per cent threshold | BS 8206-2 and CIBSE LG10 guidance |
The three verdicts
- Pass — the criterion is met with margin.
- Margin — met, but within two per cent of the limit. Small changes on site could push it out of
compliance, so it is worth knowing. Meeting a requirement exactly counts as a pass, not a margin: criteria such as Ra are stated as integers, and a product specified at exactly Ra 80 against an Ra 80 requirement is correct.
- Fail — not met.
A criterion that cannot be assessed, for example UGR when no luminaire falls within the field of view, is reported as not assessed rather than silently passed.
Corrective recommendations
Every failed check produces an action with a quantity attached, because "increase the illuminance" is not useful on its own.
Illuminance scales linearly with luminaire flux, so the required change is exact. If the task area averages 364 lx against a 500 lx requirement, multiplying output by 1.373 lands precisely on the target, which the recommendation expresses as a specific number of additional luminaires, a specific higher lumen package, or a reflectance change with the expected gain.
Uniformity advice uses the spacing-to-mounting-height ratio, computing the current ratio from the actual layout and the target spacing that would fix it, along with the grid that implies for the room.
Glare advice inverts the UGR formula. Since UGR moves as 8 log10 of the summation, clearing an excess of 3.7 points needs the summation to fall to 10^(-3.7/8), about 35 per cent of its current value. Because luminance enters squared over the projected area, that corresponds to a product at roughly 59 per cent of the current luminance at the same output. The dominant contributing luminaire is named with its share, since relocating one source is often enough.
Space types and their provenance
Criteria are grouped by category: Office, Circulation, Welfare, Technical, Industrial, Warehouse, Retail, Education, Healthcare, Hospitality, Parking and Residential. Browse them at Design criteria.
The values are reproduced for design guidance. They are not a substitute for the purchased standard: clause numbering, modifiers and national annexes change between editions, and local codes take precedence. Every value is editable, and the standards.criteria and standards.providers plugin hooks let an organisation drop in its own vetted dataset.
Dwellings fall outside EN 12464-1, which covers work places. The residential entries reflect common design practice and are labelled as such.
Cylindrical illuminance
EN 12464-1:2021 asks for a mean cylindrical illuminance of at least 50 lx in general areas and 150 lx where visual communication matters, such as offices, meeting rooms, education and healthcare. The seeded values follow that split.
Surrounding area
Where a table states no surrounding-area value, it is derived from the graded scale: a 750 lx task area implies 500 lx surroundings, 500 implies 300, 300 implies 200, 200 implies 150. Uniformity on the surrounding area is assessed against 0.40.
If you have not drawn a surround zone, the whole-room average is used as a proxy and the check says so. Draw an explicit surround zone for a formal assessment.
Lighting power density
The LPD figure shipped with each space type is not a code allowance. It is an indicative LED-era target derived from the illuminance requirement:
LPD = Em / ( efficacy * utilance * MF )
at 110 lm/W luminaire efficacy, 0.75 utilance and 0.80 maintenance factor. It is a design sanity check that catches over-lighting and poor product selection. Enter the governing figure from the local energy code in the project settings to check compliance against the real allowance.
Multi-zone spaces
A room can carry several zones, each marked as task, surround, background or excluded. Statistics are reported per zone, and a zone can carry its own space type when different activities share one space, such as a classroom with a separately lit whiteboard wall.
What compliance does not cover
- Emergency lighting, which is a separate standard and calculation.
- Flicker, stroboscopic effects and temporal light artefacts.
- Photobiological safety.
- Daylight glare probability, though excessive daylight hours are flagged.
- Colour fidelity beyond Ra, such as TM-30 or R9.
These matter on real projects. Their absence here is a scope boundary, not an implication that they are unimportant.