Lumina Lighting Design Suite
Projects New design Fixtures Criteria Reference Docs Sign in Create an account

Energy and cost

Annual energy

Energy accumulates over the same time steps the daylight model uses, so daylight-responsive dimming is evaluated against the daylight actually available in each hour:


E_kWh = sum over steps [ P(level) * scheduleFraction * hours ] / 1000

Both the controlled case and the uncontrolled reference run through the identical power model, so the reported saving isolates the control strategy rather than mixing in the driver curve. The total hours simulated are reported and should read 8760.

Driver power does not scale linearly

Dimming an LED to 50 per cent light output does not halve its input power. A fixed overhead remains in the driver, so:


P(level) = P_rated * (0.90 * level + 0.10)

This matters: a control strategy that spends most of its time at a low level saves materially less energy than a linear assumption would suggest. Zones also draw a small standby load for sensors and drivers when switched off, which is included.

Operating schedules

A schedule gives the fraction of installed load called for in each hour of a weekday, Saturday and Sunday, plus a holiday count. Fractions rather than on/off, so a background level outside working hours is modelled rather than ignored.

Presets: office, retail, education, industrial two-shift, industrial continuous, healthcare, hospitality and residential.

Days a step represents are split across day types proportionally, with holidays moved from weekdays to the Sunday profile. The reported figures are:

  • Annual energy, the headline number
  • Full-load equivalent hours, energy divided by installed load, the fairest single operating figure
  • Hours with load, hours in which the schedule calls for any output at all
  • Mean output level over the hours the installation is in use

Control strategies

| Strategy | Behaviour | | --- | --- | | None | Full output whenever the schedule calls for light | | Dimming | Continuous closed-loop daylight dimming down to the driver minimum | | Stepped | Quantised upward to the nearest of N steps | | Switching | Off once daylight alone clears the target plus a deadband | | Occupancy | Output scaled by the occupancy factor | | Dimming plus occupancy | Both together |

Daylight-responsive strategies need a daylight model, which needs glazing. Occupancy sensing does not, so it still applies in a windowless space.

A zone is judged on its sensor position when one is given, otherwise on a matching task zone, otherwise on the whole task area. A sensor in the wrong place is a common cause of disappointing measured savings, which is why the position is explicit.

Tariffs

Flat rates, or time-of-use bands with per-band rates and an optional day-type restriction. Bands that wrap midnight are handled. A demand charge per kW-month can be added, applied to the installed load.

Carbon

Operational carbon only:


kg CO2e = kWh * grid emission factor

Embodied carbon of the luminaires is not modelled, which is stated wherever the figure appears. On a modern LED installation embodied carbon is a meaningful share of the lifetime total, so treat the operational figure as one part of the picture.

Grid intensities vary by a factor of thirty between regions, from roughly 0.03 kg/kWh on a hydro-dominated grid to about 0.9 on a coal-dominated one. The shipped values are indicative recent averages; use the current published figure for the connection point.

Lighting power density

Installed load divided by design area. Reported alongside the allowance for the space type, with the margin as a percentage. Control credits that some codes permit are not applied automatically, because whether they apply depends on the code and the commissioning evidence.

Whole-life cost

Present value of a recurring annual amount over n years at discount rate r with escalation e uses the growing-annuity form:


PV = A * sum_{k=1..n} ( (1+e)^(k-1) / (1+r)^k )

Replacement years follow from the rated life and the actual annual burning hours, discounted at the year they fall due. The breakdown is capital and installation, energy, replacements and cleaning, with each element's share of the total.

On a typical LED office installation energy dominates at roughly half the whole-life cost, which is why over-lighting is expensive twice: once in capital and again every year.

When a luminaire has no unit price in the catalogue, the capital figure is understated and says so, with the count of unpriced luminaires. It is not silently invented.

The equivalent annual cost annualises the total present value over the study period, which is the figure to use when comparing options with different lives.

Reading the numbers critically

  • The uncontrolled comparison assumes the same schedule with no daylight or occupancy response. It is a

fair reference, not a measurement of an existing installation.

  • Savings depend heavily on the daylight model, which depends on the climate data. With modelled rather

than measured weather, treat the saving as indicative.

  • Occupancy factors are assumptions about how a space is used. They usually dominate the occupancy-only

saving, so they deserve more scrutiny than the lighting model does.

  • Maintenance affects energy indirectly: a design with a low maintenance factor is over-lit when new,

which constant light output control converts into a real saving that this model does not yet credit.