Clear

Circulation

5
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Circulation areas and corridors 5.1 100 0.40 28 40 50 100 1.52 3500-4000 K neutral EN12464-1
Lifts and lift lobbies 5.1 100 0.40 25 40 50 100 1.52 3500-4000 K neutral EN12464-1
Stairs, escalators, travelators 5.1 100 0.40 25 40 50 100 1.52 3500-4000 K neutral EN12464-1
Loading ramps and bays 5.1 150 0.40 25 40 50 150 2.27 3500-4000 K neutral EN12464-1
Entrance halls 5.1 200 0.40 22 80 100 150 3.03 3500-4000 K neutral EN12464-1

Education

18
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Library, bookshelves 6.5 200 0.60 19 80 100 150 3.03 3500-4000 K neutral EN12464-1
School canteen 6.5 200 0.40 22 80 100 150 3.03 3500-4000 K neutral EN12464-1
Classrooms and tutorial rooms 6.5 300 0.60 19 80 150 200 4.55 3500-4000 K neutral EN12464-1
Computer practice rooms 6.5 300 0.60 19 80 150 200 4.55 3500-4000 K neutral EN12464-1
Music practice rooms 6.5 300 0.60 19 80 150 200 4.55 3500-4000 K neutral EN12464-1
Nursery and play rooms 6.5 300 0.60 19 80 150 200 4.55 3500-4000 K neutral EN12464-1
Sports halls and gymnasiums 6.5 300 0.60 22 80 100 200 4.55 3500-4000 K neutral EN12464-1
Teachers rooms 6.5 300 0.60 19 80 150 200 4.55 3500-4000 K neutral EN12464-1
Art rooms 6.5 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Blackboard / whiteboard (vertical) 6.5 500 0.70 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Classrooms for evening and adult education 6.5 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Demonstration table 6.5 500 0.70 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Handicraft rooms and teaching workshops 6.5 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Lecture hall 6.5 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Library, reading areas 6.5 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Practical rooms and laboratories 6.5 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Art rooms in art schools 6.5 750 0.70 19 90 150 500 11.36 3500-4000 K neutral EN12464-1
Technical drawing rooms 6.5 750 0.70 16 80 150 500 11.36 3500-4000 K neutral EN12464-1

Healthcare

18
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Night watch / observation 6.6 5 — 19 80 — 50 0.08 4000 K, with 3000 K in patient areas EN12464-1
Intensive care, night watch 6.6 20 — 19 90 — 50 0.30 4000 K, with 3000 K in patient areas EN12464-1
Corridors, night 6.6 50 0.40 22 80 50 50 0.76 4000 K, with 3000 K in patient areas EN12464-1
Ward, general lighting 6.6 100 0.40 19 80 50 100 1.52 4000 K, with 3000 K in patient areas EN12464-1
Corridors, daytime 6.6 200 0.60 22 80 100 150 3.03 4000 K, with 3000 K in patient areas EN12464-1
Waiting rooms 6.6 200 0.40 22 80 100 150 3.03 4000 K, with 3000 K in patient areas EN12464-1
Scanner and imaging rooms 6.6 300 0.60 19 80 100 200 4.55 4000 K, with 3000 K in patient areas EN12464-1
Ward, reading light 6.6 300 0.60 19 80 100 200 4.55 4000 K, with 3000 K in patient areas EN12464-1
Ward, simple examination 6.6 300 0.60 19 80 100 200 4.55 4000 K, with 3000 K in patient areas EN12464-1
Consulting rooms 6.6 500 0.60 19 90 150 300 7.58 4000 K, with 3000 K in patient areas EN12464-1
Dentist, general 6.6 500 0.60 19 90 150 300 7.58 4000 K, with 3000 K in patient areas EN12464-1
Dialysis 6.6 500 0.60 19 80 150 300 7.58 4000 K, with 3000 K in patient areas EN12464-1
Laboratories and pharmacies 6.6 500 0.60 19 80 150 300 7.58 4000 K, with 3000 K in patient areas EN12464-1
Pre-op and recovery rooms 6.6 500 0.60 19 90 150 300 7.58 4000 K, with 3000 K in patient areas EN12464-1
Autopsy and mortuary 6.6 750 0.70 19 90 150 500 11.36 4000 K, with 3000 K in patient areas EN12464-1
Dentist, at the patient 6.6 1 000 0.70 19 90 150 667 15.15 4000 K, with 3000 K in patient areas EN12464-1
Examination and treatment 6.6 1 000 0.70 19 90 150 667 15.15 4000 K, with 3000 K in patient areas EN12464-1
Operating theatre, general 6.6 1 000 0.60 19 90 150 667 15.15 4000 K, with 3000 K in patient areas EN12464-1

Hospitality

8
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Guest room, general 6.4 100 0.40 22 80 50 100 1.52 2700-3000 K, warm EN12464-1
Hotel corridors 6.4 100 0.40 25 80 50 100 1.52 2700-3000 K, warm EN12464-1
Restaurant and dining room 6.4 200 0.40 22 80 100 150 3.03 2700-3000 K, warm EN12464-1
Self-service restaurant 6.4 200 0.40 22 80 100 150 3.03 2700-3000 K, warm EN12464-1
Buffet 6.4 300 0.60 22 80 150 200 4.55 2700-3000 K, warm EN12464-1
Reception and cashier desk 6.4 300 0.60 22 80 150 200 4.55 2700-3000 K, warm EN12464-1
Conference rooms 6.4 500 0.60 19 80 150 300 7.58 2700-3000 K, warm EN12464-1
Kitchen 6.4 500 0.60 22 80 150 300 7.58 2700-3000 K, warm EN12464-1

Industrial

18
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Foundry and casting 5.16 200 0.40 25 40 50 150 3.03 4000 K, cool neutral EN12464-1
Rough machining and assembly 5.23 200 0.40 25 60 50 150 3.03 4000 K, cool neutral EN12464-1
Food processing, general 5.14 300 0.60 25 80 50 200 4.55 4000 K, cool neutral EN12464-1
Galvanising and electroplating 5.23 300 0.60 25 80 50 200 4.55 4000 K, cool neutral EN12464-1
Welding 5.23 300 0.60 25 60 50 200 4.55 4000 K, cool neutral EN12464-1
Food inspection and sorting 5.14 500 0.60 25 80 100 300 7.58 4000 K, cool neutral EN12464-1
Medium machining, tolerances >= 0.1 mm 5.23 500 0.60 22 60 50 300 7.58 4000 K, cool neutral EN12464-1
Textile, weaving and spinning 5.31 500 0.60 22 80 50 300 7.58 4000 K, cool neutral EN12464-1
Fine assembly, e.g. electronics 5.23 750 0.70 19 80 100 500 11.36 4000 K, cool neutral EN12464-1
Inspection and testing 5.23 750 0.70 19 80 100 500 11.36 4000 K, cool neutral EN12464-1
Paint spraying and finishing 5.23 750 0.70 25 80 100 500 11.36 4000 K, cool neutral EN12464-1
Precision machining, tolerances < 0.1 mm 5.23 750 0.70 19 60 50 500 11.36 4000 K, cool neutral EN12464-1
Printing, composing and retouching 5.28 750 0.70 19 80 100 500 11.36 4000 K, cool neutral EN12464-1
Colour inspection 5.23 1 000 0.70 16 90 150 667 15.15 4000 K, cool neutral EN12464-1
Tool making and cutting equipment 5.23 1 000 0.70 19 60 50 667 15.15 4000 K, cool neutral EN12464-1
Very fine assembly, instrument making 5.23 1 000 0.70 16 80 100 667 15.15 4000 K, cool neutral EN12464-1
Printing, colour proofing 5.28 1 500 0.70 16 90 150 1 000 22.73 4000 K, cool neutral EN12464-1
Textile, inspection and mending 5.31 1 500 0.70 19 90 150 1 000 22.73 4000 K, cool neutral EN12464-1

Office

9
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Archives 6.2 200 0.40 25 80 50 150 3.03 3500-4000 K neutral EN12464-1
Filing, copying, circulation 6.2 300 0.40 19 80 150 200 4.55 3500-4000 K neutral EN12464-1
Print and copy room 6.2 300 0.40 22 80 50 200 4.55 3500-4000 K neutral EN12464-1
Reception desk 6.2 300 0.60 22 80 150 200 4.55 3500-4000 K neutral EN12464-1
CAD work station 6.2 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Conference and meeting rooms 6.2 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Open plan office, general 6.2 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Writing, typing, reading, data processing 6.2 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1
Technical drawing 6.2 750 0.70 16 80 150 500 11.36 3500-4000 K neutral EN12464-1

Parking

4
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Car park, parking bays 5.12 75 0.40 25 40 50 75 1.14 4000 K, cool neutral EN12464-1
Car park, traffic lanes 5.12 75 0.40 25 40 50 75 1.14 4000 K, cool neutral EN12464-1
Car park, in and out ramps (day) 5.12 300 0.40 25 40 50 200 4.55 4000 K, cool neutral EN12464-1
Car park, ticket office 5.12 300 0.60 19 80 100 200 4.55 4000 K, cool neutral EN12464-1

Residential

14
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Bedroom, general practice 100 0.40 22 80 50 100 1.52 2700-3000 K, warm RESIDENTIAL
Hall and landing practice 100 0.40 22 80 50 100 1.52 2700-3000 K, warm RESIDENTIAL
Living room, general practice 100 0.40 22 80 50 100 1.52 2700-3000 K, warm RESIDENTIAL
Stairs practice 100 0.40 22 80 50 100 1.52 2700-3000 K, warm RESIDENTIAL
Bathroom, general practice 150 0.40 22 80 50 150 2.27 2700-3000 K, warm RESIDENTIAL
Dining room practice 200 0.40 22 80 100 150 3.03 2700-3000 K, warm RESIDENTIAL
Bedroom, bedside reading practice 300 0.60 19 80 100 200 4.55 2700-3000 K, warm RESIDENTIAL
Garage and workshop practice 300 0.60 25 80 50 200 4.55 2700-3000 K, warm RESIDENTIAL
Kitchen, general practice 300 0.60 22 80 100 200 4.55 2700-3000 K, warm RESIDENTIAL
Utility and laundry practice 300 0.60 22 80 100 200 4.55 2700-3000 K, warm RESIDENTIAL
Bathroom, mirror / shaving practice 500 0.60 19 90 150 300 7.58 2700-3000 K, warm RESIDENTIAL
Home office / study practice 500 0.60 19 80 150 300 7.58 2700-3000 K, warm RESIDENTIAL
Kitchen, worktop practice 500 0.60 22 80 150 300 7.58 2700-3000 K, warm RESIDENTIAL
Living room, reading practice 500 0.60 19 80 150 300 7.58 2700-3000 K, warm RESIDENTIAL

Retail

6
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Fitting rooms 5.5 300 0.60 19 90 150 200 4.55 3000-4000 K depending on merchandise EN12464-1
Sales area, general 5.5 300 0.40 22 80 100 200 4.55 3000-4000 K depending on merchandise EN12464-1
Sales area, high-end display 5.5 500 0.60 22 90 150 300 7.58 3000-4000 K depending on merchandise EN12464-1
Supermarket aisles 5.5 500 0.60 22 80 100 300 7.58 3000-4000 K depending on merchandise EN12464-1
Till and checkout area 5.5 500 0.60 19 80 150 300 7.58 3000-4000 K depending on merchandise EN12464-1
Wrapper table 5.5 500 0.60 19 80 150 300 7.58 3000-4000 K depending on merchandise EN12464-1

Technical

5
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Store rooms and cold stores 5.4 100 0.40 25 60 50 100 1.52 4000 K, cool neutral EN12464-1
Plant rooms and switchgear rooms 5.3 200 0.40 25 60 50 150 3.03 4000 K, cool neutral EN12464-1
Despatch and packing areas 5.4 300 0.60 25 60 50 200 4.55 4000 K, cool neutral EN12464-1
Control rooms, continuously manned 5.3 500 0.60 19 80 150 300 7.58 4000 K, cool neutral EN12464-1
Telex, mail and switchboard rooms 5.3 500 0.60 19 80 150 300 7.58 4000 K, cool neutral EN12464-1

Warehouse

3
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Storage racks, unoccupied aisles 5.4 100 0.40 25 60 50 100 1.52 4000 K, cool neutral EN12464-1
Storage racks, continuously occupied 5.4 200 0.60 22 60 50 150 3.03 4000 K, cool neutral EN12464-1
Picking and order fulfilment 5.4 300 0.60 22 60 50 200 4.55 4000 K, cool neutral EN12464-1

Welfare

6
Activity or area Ēm
lx
Uo
min
UGRL
max
Ra
min
Ēz
lx
Surround
lx
LPD target
W/m²
Colour appearance Standard
Rest rooms 5.2 100 0.40 22 80 50 100 1.52 3500-4000 K neutral EN12464-1
Canteens and pantries 5.2 200 0.40 22 80 100 150 3.03 3500-4000 K neutral EN12464-1
Cloakrooms, washrooms, toilets 5.2 200 0.40 25 80 50 150 3.03 3500-4000 K neutral EN12464-1
Rooms for physical exercise 5.2 300 0.40 22 80 100 200 4.55 3500-4000 K neutral EN12464-1
Rooms for medical attention 5.2 500 0.60 19 90 150 300 7.58 3500-4000 K neutral EN12464-1
Sick bay 5.2 500 0.60 19 80 150 300 7.58 3500-4000 K neutral EN12464-1

How the criteria are applied

Ēm
Maintained average illuminance on the task area, that is initial illuminance multiplied by the maintenance factor. The task area excludes the boundary band at the walls.
Uo
Overall uniformity, Emin divided by Eavg, over the task area only.
UGRL
Unified glare rating limit per CIE 117. The worst case across a sweep of observer positions and the four cardinal viewing directions is reported.
Ra
Minimum colour rendering index of the specified products. The lowest Ra in the schedule is used.
Ēz
Mean cylindrical illuminance at 1.2 m, which governs facial modelling and interpersonal communication.
Surround
Immediate surrounding area illuminance. When a table does not state one it is derived from the graded scale in EN 12464-1.
LPD target
An indicative LED-era power density derived from the illuminance requirement at 110 lm/W luminaire efficacy, 0.75 utilance and 0.80 maintenance factor. It is a design sanity check, not a code allowance: enter the governing figure in the project settings to check against it.

More on how compliance is assessed

Standards referenced

CIBSE — CIBSE SLL Code for Lighting / Lighting Guides
Edition
current
Region
United Kingdom
Authority
Chartered Institution of Building Services Engineers

UK practice, closely aligned with EN 12464-1, with additional guidance on daylight integration, room surface illuminance and design risk.

EN12464-1 — EN 12464-1 — Light and lighting: Lighting of work places, Part 1: Indoor work places
Edition
2021
Region
Europe
Authority
CEN / European Committee for Standardization

Specifies maintained illuminance Em on the task area, overall uniformity Uo, glare limit UGRL, colour rendering Ra, and since the 2021 edition mean cylindrical illuminance Ez plus wall and ceiling illuminance for interior workplaces.

IESNA — IES Lighting Library (ANSI/IES RP series)
Edition
current
Region
North America
Authority
Illuminating Engineering Society

Recommended illuminance targets by application, expressed as horizontal and vertical targets for defined visual ages, together with uniformity guidance.

RESIDENTIAL — Residential and domestic guidance (general practice)
Edition
n/a
Region
global
Authority
General practice

Dwellings are outside the scope of EN 12464-1, which covers work places. These values reflect common design practice for domestic interiors.