Classroom
9.00 × 7.00 × 3.00 m · working plane 0.75 m · Classrooms and tutorial rooms · target 300 lx
The shaded surface is the working plane, coloured with the same scale as the plan. Luminaire stubs point along the aiming direction. Glazing is drawn in blue.
Compliance
Compliant with observationsAssessed against EN 12464-1 — Light and lighting: Lighting of work places, Part 1: Indoor work places for Education — Classrooms and tutorial rooms. 11 met, 2 with a thin margin, 0 not met, 0 not assessed.
| Criterion | Actual | Required | Margin | Verdict |
|---|---|---|---|---|
|
Maintained illuminance on the task area EN12464-1 6.5 |
432.20 lx | ≥ 300.00 | 132.20 | Pass |
|
Illuminance materially above requirement Energy efficiency |
432.20 lx | ≤ 390.00 | 132.20 | Margin |
| Design is 44% above the 300 lx requirement. Reducing output would cut energy without losing compliance. | ||||
|
Overall uniformity Uo (Emin/Eavg) on the task area EN12464-1 6.5 |
0.82 | ≥ 0.60 | 0.22 | Pass |
|
Diversity Ud (Emin/Emax) on the task area Good practice |
0.73 | ≥ 0.20 | 0.53 | Pass |
|
Unified glare rating UGR (worst observer position) CIE 117 / EN12464-1 |
18.80 | ≤ 19.00 | 0.20 | Margin |
| Swept over observer positions and the four cardinal viewing directions; the worst case is reported. Margin is under 2%: small changes on site could push this out of compliance. | ||||
|
Mean cylindrical illuminance at 1.2 m EN 12464-1 (modelling / facial recognition) |
205.70 lx | ≥ 150.00 | 55.70 | Pass |
|
Immediate surrounding area maintained illuminance EN12464-1 (surrounding area) |
366.16 lx | ≥ 200.00 | 166.16 | Pass |
|
Mean maintained illuminance on the walls EN 12464-1:2021 (interior workplaces) |
215.90 lx | ≥ 50.00 | 165.90 | Pass |
|
Mean maintained illuminance on the ceiling EN 12464-1:2021 (interior workplaces) |
115.46 lx | ≥ 30.00 | 85.46 | Pass |
|
Colour rendering index Ra of the specified luminaires EN12464-1 6.5 |
80.00 | ≥ 80.00 | 0.00 | Pass |
|
Calculation grid spacing EN 12464-1 Annex (grid), p = 0.2 x 5^(log10 d) |
0.90 m | ≤ 0.93 | 0.03 | Pass |
|
Lighting power density Energy code allowance for this space type |
3.81 W/m2 | ≤ 4.55 | 0.74 | Pass |
|
Average daylight factor BS 8206-2 / CIBSE LG10 guidance |
3.21 % | ≥ 2.00 | 1.21 | Pass |
Criteria are reproduced for design guidance. Confirm the governing values against the purchased standard and any local amendments before issuing a design.
Recommended corrections
1Trim 31% of output to cut energy
The design delivers 432 lx where 300 lx is required. Dimming to 69% keeps compliance and saves roughly 66 W.
- Set the constant-light-output level to 69% on the driver or control system.
- Or remove 1 luminaires and re-check uniformity, which will drop.
- Or specify a lower lumen package, which also reduces capital cost.
Estimated load change -66 W
Illuminance
| Area | Points | Emin | Eavg | Emax | Uo | Ud |
|---|---|---|---|---|---|---|
| Task area (compliance basis) | 48 | 353 | 432 | 483 | 0.817 | 0.732 |
| Whole room | 80 | 263 | 388 | 483 | 0.677 | 0.545 |
| Direct component | 48 | 247 | 330 | 383 | 0.747 | 0.644 |
| Interreflected component | 80 | 99 | 108 | 121 | 0.915 | 0.815 |
Zones
| Zone | Kind | Points | Emin | Eavg | Uo |
|---|---|---|---|---|---|
| Desks | task | 40 | 353 | 430 | 0.822 |
| Whiteboard approach | surround | 20 | 263 | 366 | 0.718 |
Room surfaces
| Surface | Area m² | Reflectance | Edirect | Eindirect | Etotal | Luminance |
|---|---|---|---|---|---|---|
| Ceiling | 63.0 | 80% | 0 | 115 | 115 | 29.4 cd/m² |
| Floor | 63.0 | 30% | 236 | 112 | 348 | 33.3 cd/m² |
| Wall X=0 | 21.0 | 60% | 124 | 106 | 230 | 44.0 cd/m² |
| Wall X=max | 21.0 | 60% | 124 | 106 | 230 | 44.0 cd/m² |
| Wall Y=0 | 27.0 | 60% | 92 | 110 | 202 | 38.5 cd/m² |
| Wall Y=max | 27.0 | 60% | 92 | 110 | 202 | 38.5 cd/m² |
Glare
UGR 18.8- Worst case
- UGR 18.80, looking +X
- Observer
- 1.05, 3.50 m at 1.20 m eye height
- Background luminance
- 35.0 cd/m²
- Cases assessed
- 24
Which luminaires drive the glare
| Luminaire | Distance | σ off axis | Position index p | Intensity | Luminance | Share |
|---|---|---|---|---|---|---|
| L2 | 4.27 m | 36.0° | 3.04 | 549 cd | 3 614 cd/m² | 37.7% |
| L5 | 4.27 m | 36.0° | 3.04 | 549 cd | 3 614 cd/m² | 37.7% |
| L3 | 6.92 m | 21.3° | 1.77 | 220 cd | 2 348 cd/m² | 11.0% |
| L6 | 6.92 m | 21.3° | 1.77 | 220 cd | 2 348 cd/m² | 11.0% |
| L1 | 2.55 m | 79.8° | 30.15 | 804 cd | 3 166 cd/m² | 1.4% |
| L4 | 2.55 m | 79.8° | 30.15 | 804 cd | 3 166 cd/m² | 1.4% |
UGR = 8 log₁₀[(0.25 / L_b) Σ L²ω / p²] per CIE 117. The position index p uses Guth's index via Levin's fit.
Vertical and cylindrical illuminance
Measured at 1.20 m, the eye height used for modelling and facial recognition.
| Quantity | Min | Mean | Max | Uo |
|---|---|---|---|---|
| Cylindrical Ez | 179 | 206 | 242 | 0.870 |
| Vertical Ev, plane facing +X | 141 | 215 | 321 | 0.655 |
| Vertical Ev, plane facing -X | 141 | 215 | 321 | 0.655 |
| Vertical Ev, plane facing +Y | 118 | 196 | 282 | 0.603 |
| Vertical Ev, plane facing -Y | 118 | 196 | 282 | 0.603 |
Cylindrical illuminance E_z uses E = I cos(epsilon) / (pi r^2) per source plus the mean interreflected vertical component. Vertical planes face the four cardinal directions.
Daylight
DF 3.21%3.21%
2.79%
14.6%
9.6%
Well daylit: electric lighting can be switched or dimmed for much of the day
Glazing
| Window | Wall | Orientation | Width | Sill–head | Area | Net τ | Obstruction |
|---|---|---|---|---|---|---|---|
| Window 1 | E | E (90°) | 5.40 m | 0.90–2.60 m | 9.18 m² | 0.504 | 0° |
Annual availability
57.8%
58%
73.2%
12.4%
Month by month
| Month | Occupied hours | Mean interior | Mean exterior |
|---|---|---|---|
| Jan | 221 | 340 lx | 9 226 lx |
| Feb | 200 | 647 lx | 17 131 lx |
| Mar | 221 | 1 075 lx | 28 022 lx |
| Apr | 214 | 1 374 lx | 40 277 lx |
| May | 221 | 1 579 lx | 49 497 lx |
| Jun | 214 | 1 648 lx | 54 355 lx |
| Jul | 221 | 1 694 lx | 53 767 lx |
| Aug | 221 | 1 538 lx | 47 211 lx |
| Sep | 214 | 1 241 lx | 35 362 lx |
| Oct | 221 | 854 lx | 22 324 lx |
| Nov | 214 | 445 lx | 12 013 lx |
| Dec | 221 | 272 lx | 7 460 lx |
Annual figures use 12 representative days x 24 hours, weighted by days per month, with a monthly clearness climate. Switch to the hourly model for a full 8760 step run.
Energy, carbon and cost
538kWh
€140
204kg
29.5%
- Installed load
- 240.0 W across 6 luminaires
- Power density
- 3.810 W/m², installed efficacy 130.0 lm/W
- Without controls
- 763 kWh/yr on the same power model
- Full-load equivalent
- 2 240 h/yr, mean output level 0.171
- Hours simulated
- 8 760 of 8760
Compared against the lighting power density allowance for the space type. Control credits, where a code permits them, are not applied automatically.
Control zones
| Zone | Circuit | Strategy | Target | Min output | Occupancy |
|---|---|---|---|---|---|
| Window row | C1 | dimming | 300 lx | 10% | 100% |
| Board lighting | C3 | none | 500 lx | 10% | 100% |
Whole-life cost, 20 years
| Cost element | Present value | Share |
|---|---|---|
| Capital and installation | €726 | 19.4% |
| Energy | €2,050 | 54.8% |
| Replacements | €818 | 21.9% |
| Cleaning | €150 | 4.0% |
| Total present value | €3,744 | 100% |
Discount rate 5.0%, energy escalation 2.0%, equivalent annual cost €300. All luminaires carry a unit price.
Fixture schedule
6 luminaires| Mark | Product | Code | Qty | lm | W | Total W | CCT / Ra | LLF | Cost |
|---|---|---|---|---|---|---|---|---|---|
| T1 | Generic LED Troffer 1200 5200lm UGR16 troffer, 1200 x 300 x 70 mm, circuits C1, C2 |
TRF-1200-5200 | 6 | 5 200 | 40.0 | 240 | 4000 K / Ra 80 | 0.847 | €576 |
| Total | 6 | 240 | €576 | ||||||
Method and numerical quality
Point-by-point direct (inverse square + cosine law) plus radiosity interreflection with analytic configuration factors.
- Utilance
- 0.9748 — direct 0.7029 plus interreflected 0.2719
- CU vs lamp lumens
- not applicable
- Room cavity ratio
- RCR 2.857, room index K 1.750
- Effective cavity reflectances
- ceiling 0.800, floor 0.310
- Lumen method Eavg
- 386.2 lx maintained
- Cross-check
- 0.43% from the grid average of 387.9 lx
- Flux closure
- 100.32% direct, 100.31% absorption (100% is exact)
- Solver
- 72 patches, 13 iterations, residual 7.5e-7
- Runtime
- 262 ms (from cache)
Photometry is absolute (luminaire lumens), so no bare-lamp reference exists and only utilance is defined. Published CU tables are referenced to lamp lumens and will read lower.
Note: Grid per EN 12464-1: 10 x 8 points at 0.900 x 0.875 m spacing (maximum permitted 0.929 m).
Glazing
Daylight factor plan
Lighting controls
A zone trims its circuit so daylight plus electric light reaches the target. Savings are computed hour by hour against the daylight model, not from an assumed percentage.
Maintained illuminance, lx
Download CSV| Y \ X | 0.45 | 1.35 | 2.25 | 3.15 | 4.05 | 4.95 | 5.85 | 6.75 | 7.65 | 8.55 |
|---|---|---|---|---|---|---|---|---|---|---|
| 6.56 | 263 | 290 | 316 | 332 | 329 | 329 | 332 | 316 | 290 | 263 |
| 5.69 | 354 | 410 | 445 | 462 | 461 | 461 | 462 | 445 | 410 | 354 |
| 4.81 | 371 | 427 | 465 | 483 | 482 | 482 | 483 | 465 | 427 | 371 |
| 3.94 | 318 | 353 | 388 | 408 | 403 | 403 | 408 | 388 | 353 | 318 |
| 3.06 | 318 | 353 | 388 | 408 | 403 | 403 | 408 | 388 | 353 | 318 |
| 2.19 | 371 | 427 | 465 | 483 | 482 | 482 | 483 | 465 | 427 | 371 |
| 1.31 | 354 | 410 | 445 | 462 | 461 | 461 | 462 | 445 | 410 | 354 |
| 0.44 | 263 | 290 | 316 | 332 | 329 | 329 | 332 | 316 | 290 | 263 |
Dimmed cells sit in the boundary band that EN 12464-1 excludes from the task area. Grid 10 × 8 at 0.900 m spacing (maximum permitted 0.929 m).