Open plan office
12.00 × 9.00 × 2.90 m · working plane 0.75 m · Open plan office, general · target 500 lx
The shaded surface is the working plane, coloured with the same scale as the plan. Luminaire stubs point along the aiming direction. Glazing is drawn in blue.
Compliance
CompliantAssessed against EN 12464-1 — Light and lighting: Lighting of work places, Part 1: Indoor work places for Office — Open plan office, general. 12 met, 0 with a thin margin, 0 not met, 0 not assessed.
| Criterion | Actual | Required | Margin | Verdict |
|---|---|---|---|---|
|
Maintained illuminance on the task area EN12464-1 6.2 |
537.04 lx | ≥ 500.00 | 37.04 | Pass |
|
Overall uniformity Uo (Emin/Eavg) on the task area EN12464-1 6.2 |
0.89 | ≥ 0.60 | 0.29 | Pass |
|
Diversity Ud (Emin/Emax) on the task area Good practice |
0.82 | ≥ 0.20 | 0.62 | Pass |
|
Unified glare rating UGR (worst observer position) CIE 117 / EN12464-1 |
17.30 | ≤ 19.00 | 1.70 | Pass |
|
Mean cylindrical illuminance at 1.2 m EN 12464-1 (modelling / facial recognition) |
269.78 lx | ≥ 150.00 | 119.78 | Pass |
|
Immediate surrounding area maintained illuminance EN12464-1 (surrounding area) |
494.81 lx | ≥ 300.00 | 194.81 | Pass |
|
Mean maintained illuminance on the walls EN 12464-1:2021 (interior workplaces) |
280.30 lx | ≥ 50.00 | 230.30 | Pass |
|
Mean maintained illuminance on the ceiling EN 12464-1:2021 (interior workplaces) |
149.98 lx | ≥ 30.00 | 119.98 | Pass |
|
Colour rendering index Ra of the specified luminaires EN12464-1 6.2 |
80.00 | ≥ 80.00 | 0.00 | Pass |
|
Calculation grid spacing EN 12464-1 Annex (grid), p = 0.2 x 5^(log10 d) |
1.09 m | ≤ 1.14 | 0.05 | Pass |
|
Lighting power density Energy code allowance for this space type |
4.74 W/m2 | ≤ 7.58 | 2.84 | Pass |
|
Average daylight factor BS 8206-2 / CIBSE LG10 guidance |
3.10 % | ≥ 2.00 | 1.10 | Pass |
Criteria are reproduced for design guidance. Confirm the governing values against the purchased standard and any local amendments before issuing a design.
Illuminance
| Area | Points | Emin | Eavg | Emax | Uo | Ud |
|---|---|---|---|---|---|---|
| Task area (compliance basis) | 63 | 479 | 537 | 583 | 0.892 | 0.821 |
| Whole room | 99 | 351 | 495 | 583 | 0.710 | 0.602 |
| Direct component | 63 | 344 | 407 | 457 | 0.845 | 0.753 |
| Interreflected component | 99 | 127 | 136 | 154 | 0.928 | 0.822 |
Room surfaces
| Surface | Area m² | Reflectance | Edirect | Eindirect | Etotal | Luminance |
|---|---|---|---|---|---|---|
| Ceiling | 108.0 | 80% | 0 | 150 | 150 | 38.2 cd/m² |
| Floor | 108.0 | 30% | 315 | 141 | 456 | 43.5 cd/m² |
| Wall X=0 | 26.1 | 60% | 136 | 138 | 274 | 52.4 cd/m² |
| Wall X=max | 26.1 | 60% | 136 | 138 | 274 | 52.4 cd/m² |
| Wall Y=0 | 34.8 | 60% | 148 | 138 | 286 | 54.7 cd/m² |
| Wall Y=max | 34.8 | 60% | 148 | 138 | 286 | 54.7 cd/m² |
Glare
UGR 17.3- Worst case
- UGR 17.30, looking +Y
- Observer
- 6.00, 1.20 m at 1.20 m eye height
- Background luminance
- 45.4 cd/m²
- Cases assessed
- 30
Which luminaires drive the glare
| Luminaire | Distance | σ off axis | Position index p | Intensity | Luminance | Share |
|---|---|---|---|---|---|---|
| L6 | 3.14 m | 46.2° | 4.91 | 601 cd | 3 086 cd/m² | 29.6% |
| L7 | 3.14 m | 46.2° | 4.91 | 601 cd | 3 086 cd/m² | 29.6% |
| L10 | 4.97 m | 27.1° | 2.21 | 230 cd | 1 872 cd/m² | 13.5% |
| L11 | 4.97 m | 27.1° | 2.21 | 230 cd | 1 872 cd/m² | 13.5% |
| L14 | 7.05 m | 18.8° | 1.66 | 107 cd | 1 237 cd/m² | 3.7% |
| L15 | 7.05 m | 18.8° | 1.66 | 107 cd | 1 237 cd/m² | 3.7% |
| L9 | 6.54 m | 47.4° | 3.28 | 125 cd | 1 339 cd/m² | 1.4% |
| L12 | 6.54 m | 47.4° | 3.28 | 125 cd | 1 339 cd/m² | 1.4% |
| L5 | 5.28 m | 65.7° | 7.02 | 203 cd | 1 747 cd/m² | 1.0% |
| L8 | 5.28 m | 65.7° | 7.02 | 203 cd | 1 747 cd/m² | 1.0% |
| L13 | 8.23 m | 35.8° | 2.21 | 77 cd | 1 040 cd/m² | 0.9% |
| L16 | 8.23 m | 35.8° | 2.21 | 77 cd | 1 040 cd/m² | 0.9% |
UGR = 8 log₁₀[(0.25 / L_b) Σ L²ω / p²] per CIE 117. The position index p uses Guth's index via Levin's fit.
Vertical and cylindrical illuminance
Measured at 1.20 m, the eye height used for modelling and facial recognition.
| Quantity | Min | Mean | Max | Uo |
|---|---|---|---|---|
| Cylindrical Ez | 225 | 270 | 313 | 0.833 |
| Vertical Ev, plane facing +X | 167 | 272 | 346 | 0.615 |
| Vertical Ev, plane facing -X | 167 | 272 | 346 | 0.615 |
| Vertical Ev, plane facing +Y | 174 | 268 | 340 | 0.647 |
| Vertical Ev, plane facing -Y | 174 | 268 | 340 | 0.647 |
Cylindrical illuminance E_z uses E = I cos(epsilon) / (pi r^2) per source plus the mean interreflected vertical component. Vertical planes face the four cardinal directions.
Daylight
DF 3.10%3.10%
2.86%
13.3%
11.8%
Well daylit: electric lighting can be switched or dimmed for much of the day
Glazing
| Window | Wall | Orientation | Width | Sill–head | Area | Net τ | Obstruction |
|---|---|---|---|---|---|---|---|
| Window 1 | S | S (180°) | 4.50 m | 0.90–2.50 m | 7.20 m² | 0.504 | 0° |
| Window 2 | S | S (180°) | 4.50 m | 0.90–2.50 m | 7.20 m² | 0.504 | 0° |
Annual availability
55.5%
62%
71.6%
17.0%
Month by month
| Month | Occupied hours | Mean interior | Mean exterior |
|---|---|---|---|
| Jan | 221 | 503 lx | 9 376 lx |
| Feb | 200 | 1 007 lx | 16 706 lx |
| Mar | 221 | 1 406 lx | 26 722 lx |
| Apr | 214 | 1 786 lx | 38 046 lx |
| May | 221 | 1 880 lx | 46 640 lx |
| Jun | 214 | 1 989 lx | 51 217 lx |
| Jul | 221 | 2 027 lx | 50 729 lx |
| Aug | 221 | 2 004 lx | 44 662 lx |
| Sep | 214 | 1 832 lx | 33 592 lx |
| Oct | 221 | 1 359 lx | 21 500 lx |
| Nov | 214 | 816 lx | 11 967 lx |
| Dec | 221 | 474 lx | 7 731 lx |
Annual figures use 12 representative days x 24 hours, weighted by days per month, with a monthly clearness climate. Switch to the hourly model for a full 8760 step run.
Energy, carbon and cost
934kWh
£234
193kg
55.3%
- Installed load
- 512.0 W across 16 luminaires
- Power density
- 4.741 W/m², installed efficacy 125.0 lm/W
- Without controls
- 2 088 kWh/yr on the same power model
- Full-load equivalent
- 1 824 h/yr, mean output level 0.118
- Hours simulated
- 8 760 of 8760
Compared against the lighting power density allowance for the space type. Control credits, where a code permits them, are not applied automatically.
Control zones
| Zone | Circuit | Strategy | Target | Min output | Occupancy |
|---|---|---|---|---|---|
| Window row daylight dimming | C1 | dimming | 500 lx | 10% | 100% |
| Inner rows | C2 | dimming+occupancy | 500 lx | 10% | 85% |
Whole-life cost, 20 years
| Cost element | Present value | Share |
|---|---|---|
| Capital and installation | £1,232 | 17.7% |
| Energy | £3,424 | 49.3% |
| Replacements | £1,891 | 27.2% |
| Cleaning | £399 | 5.7% |
| Total present value | £6,946 | 100% |
Discount rate 5.0%, energy escalation 2.0%, equivalent annual cost £557. All luminaires carry a unit price.
Fixture schedule
16 luminaires| Mark | Product | Code | Qty | lm | W | Total W | CCT / Ra | LLF | Cost |
|---|---|---|---|---|---|---|---|---|---|
| T1 | Generic LED Panel 600x600 4000lm recessed, 600 x 600 x 30 mm, circuits C1, C2 |
PNL-600-4000 | 16 | 4 000 | 32.0 | 512 | 4000 K / Ra 80 | 0.847 | £832 |
| Total | 16 | 512 | £832 | ||||||
Method and numerical quality
Point-by-point direct (inverse square + cosine law) plus radiosity interreflection with analytic configuration factors.
- Utilance
- 1.0391 — direct 0.7515 plus interreflected 0.2876
- CU vs lamp lumens
- not applicable
- Room cavity ratio
- RCR 2.090, room index K 2.392
- Effective cavity reflectances
- ceiling 0.800, floor 0.311
- Lumen method Eavg
- 492.7 lx maintained
- Cross-check
- 0.44% from the grid average of 494.8 lx
- Flux closure
- 100.41% direct, 100.39% absorption (100% is exact)
- Solver
- 72 patches, 13 iterations, residual 5.1e-7
- Runtime
- 313 ms (from cache)
Photometry is absolute (luminaire lumens), so no bare-lamp reference exists and only utilance is defined. Published CU tables are referenced to lamp lumens and will read lower.
Note: Grid per EN 12464-1: 11 x 9 points at 1.091 x 1.000 m spacing (maximum permitted 1.136 m).
Glazing
Daylight factor plan
Lighting controls
A zone trims its circuit so daylight plus electric light reaches the target. Savings are computed hour by hour against the daylight model, not from an assumed percentage.
Maintained illuminance, lx
Download CSV| Y \ X | 0.55 | 1.64 | 2.73 | 3.82 | 4.91 | 6.00 | 7.09 | 8.18 | 9.27 | 10.36 | 11.45 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 8.50 | 351 | 408 | 422 | 439 | 445 | 437 | 445 | 439 | 422 | 408 | 351 |
| 7.50 | 404 | 479 | 496 | 514 | 521 | 511 | 521 | 514 | 496 | 479 | 404 |
| 6.50 | 434 | 520 | 531 | 554 | 564 | 547 | 564 | 554 | 531 | 520 | 434 |
| 5.50 | 443 | 524 | 545 | 565 | 572 | 563 | 572 | 565 | 545 | 524 | 443 |
| 4.50 | 448 | 537 | 549 | 573 | 584 | 566 | 584 | 573 | 549 | 537 | 448 |
| 3.50 | 443 | 524 | 545 | 565 | 572 | 563 | 572 | 565 | 545 | 524 | 443 |
| 2.50 | 434 | 520 | 531 | 554 | 564 | 547 | 564 | 554 | 531 | 520 | 434 |
| 1.50 | 404 | 479 | 496 | 514 | 521 | 511 | 521 | 514 | 496 | 479 | 404 |
| 0.50 | 351 | 408 | 422 | 439 | 445 | 437 | 445 | 439 | 422 | 408 | 351 |
Dimmed cells sit in the boundary band that EN 12464-1 excludes from the task area. Grid 11 × 9 at 1.091 m spacing (maximum permitted 1.136 m).