Warehouse
30.00 × 20.00 × 9.00 m · working plane 0.00 m · Storage racks, continuously occupied · target 200 lx
The shaded surface is the working plane, coloured with the same scale as the plan. Luminaire stubs point along the aiming direction. Glazing is drawn in blue.
Compliance
Compliant with observationsAssessed against EN 12464-1 — Light and lighting: Lighting of work places, Part 1: Indoor work places for Warehouse — Storage racks, continuously occupied. 10 met, 1 with a thin margin, 0 not met, 0 not assessed.
| Criterion | Actual | Required | Margin | Verdict |
|---|---|---|---|---|
|
Maintained illuminance on the task area EN12464-1 5.4 |
249.74 lx | ≥ 200.00 | 49.74 | Pass |
|
Overall uniformity Uo (Emin/Eavg) on the task area EN12464-1 5.4 |
0.85 | ≥ 0.60 | 0.25 | Pass |
|
Diversity Ud (Emin/Emax) on the task area Good practice |
0.76 | ≥ 0.20 | 0.56 | Pass |
|
Unified glare rating UGR (worst observer position) CIE 117 / EN12464-1 |
20.69 | ≤ 22.00 | 1.31 | Pass |
|
Mean cylindrical illuminance at 1.2 m EN 12464-1 (modelling / facial recognition) |
66.57 lx | ≥ 50.00 | 16.57 | Pass |
|
Immediate surrounding area maintained illuminance EN12464-1 (surrounding area) |
225.16 lx | ≥ 150.00 | 75.16 | Pass |
|
Mean maintained illuminance on the walls EN 12464-1:2021 (interior workplaces) |
64.20 lx | ≥ 50.00 | 14.20 | Pass |
|
Mean maintained illuminance on the ceiling EN 12464-1:2021 (interior workplaces) |
32.10 lx | ≥ 30.00 | 2.10 | Pass |
|
Colour rendering index Ra of the specified luminaires EN12464-1 5.4 |
80.00 | ≥ 60.00 | 20.00 | Pass |
|
Calculation grid spacing EN 12464-1 Annex (grid), p = 0.2 x 5^(log10 d) |
2.14 m | ≤ 2.16 | 0.01 | Margin |
| A grid coarser than the maximum can miss the true minimum. Margin is under 2%: small changes on site could push this out of compliance. | ||||
|
Lighting power density Energy code allowance for this space type |
2.50 W/m2 | ≤ 3.03 | 0.53 | Pass |
Criteria are reproduced for design guidance. Confirm the governing values against the purchased standard and any local amendments before issuing a design.
Illuminance
| Area | Points | Emin | Eavg | Emax | Uo | Ud |
|---|---|---|---|---|---|---|
| Task area (compliance basis) | 96 | 213 | 250 | 279 | 0.852 | 0.763 |
| Whole room | 140 | 125 | 225 | 279 | 0.557 | 0.450 |
| Direct component | 96 | 194 | 232 | 261 | 0.836 | 0.742 |
| Interreflected component | 140 | 17 | 19 | 21 | 0.922 | 0.816 |
Room surfaces
| Surface | Area m² | Reflectance | Edirect | Eindirect | Etotal | Luminance |
|---|---|---|---|---|---|---|
| Ceiling | 600.0 | 50% | 0 | 32 | 32 | 5.1 cd/m² |
| Floor | 600.0 | 20% | 207 | 19 | 225 | 14.4 cd/m² |
| Wall X=0 | 180.0 | 30% | 38 | 26 | 64 | 6.1 cd/m² |
| Wall X=max | 180.0 | 30% | 38 | 26 | 64 | 6.1 cd/m² |
| Wall Y=0 | 270.0 | 30% | 38 | 27 | 64 | 6.2 cd/m² |
| Wall Y=max | 270.0 | 30% | 38 | 27 | 64 | 6.2 cd/m² |
Glare
UGR 20.7- Worst case
- UGR 20.69, looking +X
- Observer
- 1.20, 10.00 m at 1.20 m eye height
- Background luminance
- 9.9 cd/m²
- Cases assessed
- 24
Which luminaires drive the glare
| Luminaire | Distance | σ off axis | Position index p | Intensity | Luminance | Share |
|---|---|---|---|---|---|---|
| L7 | 10.68 m | 43.1° | 6.39 | 1 532 cd | 18 305 cd/m² | 39.5% |
| L6 | 7.52 m | 76.2° | 44.94 | 8 488 cd | 71 364 cd/m² | 34.9% |
| L2 | 12.59 m | 51.7° | 6.32 | 680 cd | 9 573 cd/m² | 6.8% |
| L12 | 12.59 m | 51.7° | 6.32 | 680 cd | 9 573 cd/m² | 6.8% |
| L1 | 10.05 m | 79.7° | 31.20 | 2 072 cd | 23 285 cd/m² | 3.2% |
| L11 | 10.05 m | 79.7° | 31.20 | 2 072 cd | 23 285 cd/m² | 3.2% |
| L8 | 15.61 m | 27.9° | 3.04 | 235 cd | 4 106 cd/m² | 2.8% |
| L3 | 16.98 m | 35.6° | 3.05 | 156 cd | 2 963 cd/m² | 1.1% |
| L13 | 16.98 m | 35.6° | 3.05 | 156 cd | 2 963 cd/m² | 1.1% |
| L9 | 21.10 m | 20.2° | 2.17 | 53 cd | 1 261 cd/m² | 0.2% |
| L4 | 22.13 m | 26.5° | 2.15 | 43 cd | 1 064 cd/m² | 0.1% |
| L14 | 22.13 m | 26.5° | 2.15 | 43 cd | 1 064 cd/m² | 0.1% |
UGR = 8 log₁₀[(0.25 / L_b) Σ L²ω / p²] per CIE 117. The position index p uses Guth's index via Levin's fit.
Vertical and cylindrical illuminance
Measured at 1.20 m, the eye height used for modelling and facial recognition.
| Quantity | Min | Mean | Max | Uo |
|---|---|---|---|---|
| Cylindrical Ez | 48 | 67 | 82 | 0.717 |
| Vertical Ev, plane facing +X | 27 | 67 | 97 | 0.399 |
| Vertical Ev, plane facing -X | 27 | 67 | 97 | 0.399 |
| Vertical Ev, plane facing +Y | 26 | 65 | 99 | 0.404 |
| Vertical Ev, plane facing -Y | 26 | 65 | 99 | 0.404 |
Cylindrical illuminance E_z uses E = I cos(epsilon) / (pi r^2) per source plus the mean interreflected vertical component. Vertical planes face the four cardinal directions.
Energy, carbon and cost
6 917kWh
$865
2 559kg
12.5%
- Installed load
- 1 500.0 W across 15 luminaires
- Power density
- 2.500 W/m², installed efficacy 150.0 lm/W
- Without controls
- 7 905 kWh/yr on the same power model
- Full-load equivalent
- 4 611 h/yr, mean output level 0.473
- Hours simulated
- 8 760 of 8760
Compared against the lighting power density allowance for the space type. Control credits, where a code permits them, are not applied automatically.
Control zones
| Zone | Circuit | Strategy | Target | Min output | Occupancy |
|---|---|---|---|---|---|
| Aisle occupancy | C1 | occupancy | 200 lx | 10% | 55% |
Whole-life cost, 20 years
| Cost element | Present value | Share |
|---|---|---|
| Capital and installation | $2,595 | 14.1% |
| Energy | $12,679 | 68.8% |
| Replacements | $2,777 | 15.1% |
| Cleaning | $374 | 2.0% |
| Total present value | $18,425 | 100% |
Discount rate 5.0%, energy escalation 2.0%, equivalent annual cost $1,478. All luminaires carry a unit price.
Fixture schedule
15 luminaires| Mark | Product | Code | Qty | lm | W | Total W | CCT / Ra | LLF | Cost |
|---|---|---|---|---|---|---|---|---|---|
| T1 | Generic LED High Bay 100W 15000lm 60deg highbay, 350 x 350 x 140 mm, circuits C1, C2 |
HB-100-60 | 15 | 15 000 | 100.0 | 1 500 | 5000 K / Ra 80 | 0.885 | $2,220 |
| Total | 15 | 1 500 | $2,220 | ||||||
Method and numerical quality
Point-by-point direct (inverse square + cosine law) plus radiosity interreflection with analytic configuration factors.
- Utilance
- 0.8530 — direct 0.7825 plus interreflected 0.0705
- CU vs lamp lumens
- not applicable
- Room cavity ratio
- RCR 3.542, room index K 1.412
- Effective cavity reflectances
- ceiling 0.465, floor 0.200
- Lumen method Eavg
- 224.0 lx maintained
- Cross-check
- 0.53% from the grid average of 225.2 lx
- Flux closure
- 100.55% direct, 100.55% absorption (100% is exact)
- Solver
- 72 patches, 8 iterations, residual 2.2e-7
- Runtime
- 166 ms (from cache)
Photometry is absolute (luminaire lumens), so no bare-lamp reference exists and only utilance is defined. Published CU tables are referenced to lamp lumens and will read lower.
Note: Grid per EN 12464-1: 14 x 10 points at 2.143 x 2.000 m spacing (maximum permitted 2.155 m).
Glazing
No glazing defined, so the daylight model is skipped. Add a window to get daylight factors, annual availability and daylight-linked control savings.
Lighting controls
A zone trims its circuit so daylight plus electric light reaches the target. Savings are computed hour by hour against the daylight model, not from an assumed percentage.
Maintained illuminance, lx
Download CSV| Y \ X | 1.07 | 3.21 | 5.36 | 7.50 | 9.64 | 11.79 | 13.93 | 16.07 | 18.21 | 20.36 | 22.50 | 24.64 | 26.79 | 28.93 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 19.00 | 125 | 160 | 171 | 180 | 185 | 182 | 186 | 186 | 182 | 185 | 180 | 171 | 160 | 125 |
| 17.00 | 164 | 213 | 225 | 237 | 244 | 238 | 244 | 244 | 238 | 244 | 237 | 225 | 213 | 164 |
| 15.00 | 174 | 225 | 240 | 252 | 259 | 254 | 260 | 260 | 254 | 259 | 252 | 240 | 225 | 174 |
| 13.00 | 175 | 226 | 243 | 255 | 262 | 258 | 263 | 263 | 258 | 262 | 255 | 243 | 226 | 175 |
| 11.00 | 186 | 241 | 257 | 270 | 278 | 272 | 279 | 279 | 272 | 278 | 270 | 257 | 241 | 186 |
| 9.00 | 186 | 241 | 257 | 270 | 278 | 272 | 279 | 279 | 272 | 278 | 270 | 257 | 241 | 186 |
| 7.00 | 175 | 226 | 243 | 255 | 262 | 258 | 263 | 263 | 258 | 262 | 255 | 243 | 226 | 175 |
| 5.00 | 174 | 225 | 240 | 252 | 259 | 254 | 260 | 260 | 254 | 259 | 252 | 240 | 225 | 174 |
| 3.00 | 164 | 213 | 225 | 237 | 244 | 238 | 244 | 244 | 238 | 244 | 237 | 225 | 213 | 164 |
| 1.00 | 125 | 160 | 171 | 180 | 185 | 182 | 186 | 186 | 182 | 185 | 180 | 171 | 160 | 125 |
Dimmed cells sit in the boundary band that EN 12464-1 excludes from the task area. Grid 14 × 10 at 2.143 m spacing (maximum permitted 2.155 m).